| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/22/2016 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 08/22/2016 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 08/23/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/23/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the exhaust flow rate for the women's second level restroom to provide a minimum of 50 CFM per fixture (currently shown as 100 CFM for three fixtures). 2. Provide the sequence of operation for the new exhaust fan ("connect fan to existing control"). |
| 08/23/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A1.0; FIRST FLOOR REFERENCE PLAN: AT THE NEW SHOWER (ROLL-IN TYPE WITH SEAT), PLEASE PROVIDE DIMENSIONED DETAILS FOLLOWING THE ICC/ANSI SECTIONS 608, 609, AND 610 FOR GRAB BARS, CONTROL LOCATION, AND HANDSHOWER LOCATION (IN ADDITION TO DETAILS ON SHEET A3.0). 2. SHEET A1.0; FIRST FLOOR REFERENCE PLAN: THE ICC/ANSI REQUIRES A 3'-0" CLEAR OPENING INTO THE SHOWER (FIGURE 608.2.3). THE PLAN INDICATES DOOR 102A INTO THE SHOWER IS A 3'-0" DOOR SIZE. WILL THIS PROVIDE A CLEAR 3'-0" WIDTH? PLEASE VERIFY. 3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 08/23/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 08/23/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Verify that the water velocity in the 1/2" cold water supply to the eyewash P6 will not exceed 8 feet per second. |
| 08/23/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/24/2016 | MARTIN BROWN | FIRE | REVIEW | Approved |