Permit Number: T16CM06469
Parcel: 10712189D

Address:
308 W GLENN ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM06469
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/22/2016 ANDREW CONNOR ZONING REVIEW Approved
08/22/2016 LOREN MAKUS ENGINEERING REVIEW Approved
08/23/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
08/23/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the exhaust flow rate for the women's second level restroom to provide a minimum of 50 CFM per fixture (currently shown as 100 CFM for three fixtures).
2. Provide the sequence of operation for the new exhaust fan ("connect fan to existing control").
08/23/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A1.0; FIRST FLOOR REFERENCE PLAN: AT THE NEW SHOWER (ROLL-IN TYPE WITH SEAT), PLEASE PROVIDE DIMENSIONED DETAILS FOLLOWING THE ICC/ANSI SECTIONS 608, 609, AND 610 FOR GRAB BARS, CONTROL LOCATION, AND HANDSHOWER LOCATION (IN ADDITION TO DETAILS ON SHEET A3.0).
2. SHEET A1.0; FIRST FLOOR REFERENCE PLAN: THE ICC/ANSI REQUIRES A 3'-0" CLEAR OPENING INTO THE SHOWER (FIGURE 608.2.3). THE PLAN INDICATES DOOR 102A INTO THE SHOWER IS A 3'-0" DOOR SIZE. WILL THIS PROVIDE A CLEAR 3'-0" WIDTH? PLEASE VERIFY.
3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
08/23/2016 ROBERT SHERRY WATER REVIEW Completed
08/23/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Verify that the water velocity in the 1/2" cold water supply to the eyewash P6 will not exceed 8 feet per second.
08/23/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/24/2016 MARTIN BROWN FIRE REVIEW Approved