Permit Number: T16CM06427
Parcel: 12213055E

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM06427
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/19/2016 ANDREW CONNOR ZONING REVIEW Completed
08/19/2016 ERIC NEWCOMB MECHANICAL-COMMERCIAL REVIEW Passed
08/19/2016 ARUIZ1 ELECTRICAL-COMMERCIAL REVIEW Approved
08/19/2016 PAUL BAUGHMAN ENGINEERING REVIEW Completed
08/19/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEETS S1.1 AND S2.1 HAVE NOTES "PRELIMINARY NOT FOR CONSTRUCTION OR RECORDING". PLEASE REMOVE THE NOTE.
2. SHEET S2.1 (BEAM SCHEDULE); STRUCTURAL CALCULATIONS (PAGE 1); BEAM B3 IN THE CALCULATIONS INDICATES A W12X40, WHILE THE PLAN SCHEDULE INDICATES A W12X50. PLEASE CLARIFY.
08/19/2016 ENEWCOM1 WATER REVIEW Passed
08/19/2016 ERIC NEWCOMB PLUMBING-COMMERCIAL REVIEW Passed
08/19/2016 MARTIN BROWN FIRE REVIEW Approved
08/19/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed