Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T16CM06402
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/03/2017 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 01/17/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 12/21/16 Comments: 1. Alterations of an existing building in which the existing ceiling or wall cavities are exposed, shall have the exposed cavities filled with insulation. Reference: Section C101.4.3, IECC 2012. 2. Provide the air infiltration rate for the new skylights as tested per NFRC 400 or AAMA/WDMA/CSA 101/IS2 A440. Reference: Section R402.4.3, IECC 2012. 3. Provide mechanical ventilation for the building. Reference: Section 401.2, 403.2.1 (3), 403.3, Table 403.3, IMC 2012 and Sections R402.4.1.2 and R403.5, IECC 2012. (See also the building code analysis on sheet A0.0.) 4. Show the size, routing, and termination of the condensate drain for HP-A. Reference: Section 307.2.1, IMC 2012 as amended by the City of Tucson. 5. Show how the clothes dryer exhaust ducts are able to maintain the fire-resistance-rating of the floor-ceiling assemblies that they penetrate and the fire-resistance-rated separation walls in which they are located. Reference: Section 504.2, IMC 2012. 6. Show how the dryer installation complies with Section 504.5, IMC 2012 for make-up air. 7. Provide signage indicating the total equivalent length of the concealed dryer exhaust duct. Reference: Section 504.6.5, IMC 2012. |
| 01/17/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 12/21/16 Comments: 1. Provide a letter from Tucson Water stating what the minimum daily service pressure will be for this building. [Initial comment: Verify the minimum available water pressure for this address with Tucson Water; the data from Tucson Water appears to show a pressure range of 46 to 53 PSI. Revise the water pressure calculations as required.] 2. The dimensioned building section on sheet A4.0 shows the third floor to be 24'-0" above the finished first floor. Assuming a 6'-0" height for the shower outlet, the static lift will be at least 30-feet. [Initial comment: Verify the static lift used in the water pressure calculations The water meter is at least 12" below grade, the third floor is 24-feet above grade, and the highest outlet is approximately 6-feet above the third floor. Reference: Section 604.1, IPC 2012, as amended by the City of Tucson.] |
| 01/17/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. PREVIOUS COMMENT 9; SHEET A0.0; BUILDING CODES (ACCESSIBILITY): THE FINAL NOTE IN THIS SECTION REFERENCES SHEET A0.1 FOR ADDITIONAL ADA COMPLIANCE. PLEASE REVISE OR REMOVE THAT REFERENCE. 2. PREVIOUS COMMENT 10; SHEET A0.0 (BUILDING CODES); ACCESSIBILITY: THE ACCESSIBLE UNIT ON SHEET A1.3 (THIRD FLOOR PLAN) IS NOT INDICATED. PLEASE PROVIDE. 3. PREVIOUS COMMENT 34; SHEET A5.1; ELEVATION 11D: THE HORIZONTAL BAR BEHIND THE WATER CLOSET DOES NOT MEET THE REQUIRED LENGTH PER THE ICC/ANSI FIGURE 604.5.2. PLEASE REVISE. 4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 01/19/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |