Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM06339
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/15/2016 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 08/15/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 08/15/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
| 08/15/2016 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
| 08/15/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. FLOOR PLAN; CLASSROOM IN NORTHWEST CORNER OF BUILDING: TO MAKE THE CORRIDOR PART OF THE CLASSROOM, PLEASE REMOVE AT LEAST 50% OF THE WALL LENGTH ALONG THE EAST SIDE OF THE CLASSROOM, OPENING THAT ROOM TO THE CORRIDOR. |
| 08/15/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 08/15/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 08/15/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/16/2016 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | Occupant load for classroom at south of building appears to exceed 50. Please perform calculations and annotate on plans occupant load for the classroom. Door swing may be need to be in the direction of egress. Indicate on plans a directional exit sign in hallway leading into lobby. Does building contain a fire alarm system? Please review section 1103.7 and 1103.7.1 of the 2012 IFC and clarify on plans. Also, please address building review comments. |