Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T16CM06321
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/09/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEETS S3.0 AND S3.1; PROFILES: PLEASE REVISE THE DETAIL REFERENCES ON THESE SHEETS. 2. SHEET S4.0 (DETAIL 101 ALT); STRUCTURAL CALCULATIONS (BASE PLATE DESIGN PAGE 1/5): THE CALCULATIONS INDICATE A 24.00" X 24.00" X 2.25" COLUMN BASE PLATE FOR FRAME P1, WHILE THE DETAIL INDICATES A 2" X 24" X 2'-0" PLATE (NOTE 3). PLEASE COORDINATE. 3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 09/20/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |