Review Date Reviewer's Name Type of Review Description Status Comments
09/09/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEETS S3.0 AND S3.1; PROFILES: PLEASE REVISE THE DETAIL REFERENCES ON THESE SHEETS.
2. SHEET S4.0 (DETAIL 101 ALT); STRUCTURAL CALCULATIONS (BASE PLATE DESIGN PAGE 1/5): THE CALCULATIONS INDICATE A 24.00" X 24.00" X 2.25" COLUMN BASE PLATE FOR FRAME P1, WHILE THE DETAIL INDICATES A 2" X 24" X 2'-0" PLATE (NOTE 3). PLEASE COORDINATE.
3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
09/20/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved