Permit Number: T16CM06270
Parcel: 126134680

Address:
4509 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T16CM06270
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/15/2016 KEN BROUILLETTE FIRE REVIEW Reqs Change Sheet A1:
1. Section 1018.1 Corridors. The corridors called out on the plan require a 1 hr rating perTable 1018.1 which includes the protection of openings.
2. Section 1008.1.10 Panic Hardware. None of the egress doors out of the assembly indicate that panic hardware is existing or will be provided.
Sheet E1:
1. Corridor 103 does not appear to have emergency egress lighting.

3. Please indicate if any other Group A occupancies are within the entire building. This is to determine if Section 907.2.1 needs to be addressed.

4. Please indicate the Group A-3 occupancy "fire area" for the building. It is the aggreagate floor area enclosed and bounded by fire walls, fire barriers, exterior walls or horizontal assemblies of a building. Areas of the building not provided with provided with surrounding walls shall be included in the fire Group A-3 Fire Area.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/15/2016 FERNE RODRIGUEZ OUT TO CUSTOMER Completed