| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/15/2016 | KEN BROUILLETTE | FIRE | REVIEW | Reqs Change | Sheet A1: 1. Section 1018.1 Corridors. The corridors called out on the plan require a 1 hr rating perTable 1018.1 which includes the protection of openings. 2. Section 1008.1.10 Panic Hardware. None of the egress doors out of the assembly indicate that panic hardware is existing or will be provided. Sheet E1: 1. Corridor 103 does not appear to have emergency egress lighting. 3. Please indicate if any other Group A occupancies are within the entire building. This is to determine if Section 907.2.1 needs to be addressed. 4. Please indicate the Group A-3 occupancy "fire area" for the building. It is the aggreagate floor area enclosed and bounded by fire walls, fire barriers, exterior walls or horizontal assemblies of a building. Areas of the building not provided with provided with surrounding walls shall be included in the fire Group A-3 Fire Area. |