Permit Number: T16CM06145
Parcel: 11012007B

Address:
5151 E GRANT RD

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T16CM06145
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/12/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide a complete panel schedule and location of the panel. The complete panel schedule must correlate with the branch circuits, OCPD's, and devices (outlets) for the proposed work. Ref: 2012 IBC 107.2.1, 2011 NEC. City of Tucson Commercial Plan Submittal Requirements can be downloaded from www.tucsonaz.gov.
09/12/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
09/12/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
09/13/2017 ARUIZ1 APPROVAL SHELF Completed
09/13/2017 ARUIZ1 OUT TO CUSTOMER Completed