Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T16CM06145
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/12/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide a complete panel schedule and location of the panel. The complete panel schedule must correlate with the branch circuits, OCPD's, and devices (outlets) for the proposed work. Ref: 2012 IBC 107.2.1, 2011 NEC. City of Tucson Commercial Plan Submittal Requirements can be downloaded from www.tucsonaz.gov. |
| 09/12/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 09/12/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/13/2017 | ARUIZ1 | APPROVAL SHELF | Completed |
| 09/13/2017 | ARUIZ1 | OUT TO CUSTOMER | Completed |