Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM06088
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/18/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/18/2016 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 08/18/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Revise the ventilation calculations. The outside air per person is to be added to the outside air per square foot (see equation 4-1, Section 403.3.1, IMC 2012). The total amount of outside air (Vbz) is to be divided by the zone air distribution effectiveness (Ez - see equation 4-2, Section 403.3.3, IMC 2012). [Initial comment: Provide ventilation calculations per Section 403.3, IMC 2012.] |
| 08/18/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Specify the service sink and faucet that will be installed. Show how backflow protection will be provided with a "short hose" being attached to the faucet of the service sink. Reference: Section 608.15.4.2, IPC 2012. [Initial comment: Provide the minimum plumbing fixtures required by Section 2902, IBC 2012.] |
| 08/18/2016 | ROBERT SHERRY | WATER | REVIEW | Completed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/22/2016 | KROBLES1 | OUT TO CUSTOMER | Completed |