Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T16CM06088
Parcel: 12419026C

Address:
1881 E 18TH ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM06088
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/18/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/18/2016 MARTIN BROWN FIRE REVIEW Approved
08/18/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Revise the ventilation calculations. The outside air per person is to be added to the outside air per square foot (see equation 4-1, Section 403.3.1, IMC 2012). The total amount of outside air (Vbz) is to be divided by the zone air distribution effectiveness (Ez - see equation 4-2, Section 403.3.3, IMC 2012). [Initial comment: Provide ventilation calculations per Section 403.3, IMC 2012.]
08/18/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Specify the service sink and faucet that will be installed. Show how backflow protection will be provided with a "short hose" being attached to the faucet of the service sink. Reference: Section 608.15.4.2, IPC 2012. [Initial comment: Provide the minimum plumbing fixtures required by Section 2902, IBC 2012.]
08/18/2016 ROBERT SHERRY WATER REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
08/22/2016 KROBLES1 OUT TO CUSTOMER Completed