Review Details: COMMERCIAL - TI
Permit Number - T16CM06088
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/03/2016 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 08/03/2016 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 08/04/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide the minimum plumbing fixtures required by Section 2902, IBC 2012. |
| 08/04/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide ventilation calculations per Section 403.3, IMC 2012. |
| 08/04/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A1; FLOOR PLAN: TWO EXITS ARE REQUIRED FOR THIS OCCUPANCY LOAD. PER THE IBC SECTION 1014.2(4), EGRESS CAN NOT PASS THROUGH STORAGE ROOMS UNLESS THE FOUR REQUIREMENTS OF EXCEPTION 2 ARE MET. PLEASE INDICATE ON THE DRAWING HOW THESE REQUIREMENTS ARE SATISFIED. INCLUDE NOTES AND DETAILS. 2. SHEET A1; OCCUPANCY LOAD: PLEASE REVIEW THE STATED OCCUPANCY LOAD. USING THE IBC TABLE 1004.1.2, USE 30 SF PER OCCUPANT, AND REVISE THE OCCUPANCY LOAD ON THE DRAWINGS. 3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 08/04/2016 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Provide the water meter size and serial number. Show the location of the water meter and the backflow preventer |
| 08/04/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/05/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/17/2016 | ARUIZ1 | FIRE | REVIEW | Needs Review | Occupant load appears to be calculated incorrectly. Please review numbers. If occupant load has been calculated incorrectly, an additional exit will be required. Exiting through storage area is generally not allowed, unless specific guidelines are followed. |