Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16CM06088
Parcel: 12419026C

Address:
1881 E 18TH ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM06088
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/03/2016 STEVE SHIELDS ZONING REVIEW Approved
08/03/2016 LOREN MAKUS ENGINEERING REVIEW Approved
08/04/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide the minimum plumbing fixtures required by Section 2902, IBC 2012.
08/04/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide ventilation calculations per Section 403.3, IMC 2012.
08/04/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A1; FLOOR PLAN: TWO EXITS ARE REQUIRED FOR THIS OCCUPANCY LOAD. PER THE IBC SECTION 1014.2(4), EGRESS CAN NOT PASS THROUGH STORAGE ROOMS UNLESS THE FOUR REQUIREMENTS OF EXCEPTION 2 ARE MET. PLEASE INDICATE ON THE DRAWING HOW THESE REQUIREMENTS ARE SATISFIED. INCLUDE NOTES AND DETAILS.
2. SHEET A1; OCCUPANCY LOAD: PLEASE REVIEW THE STATED OCCUPANCY LOAD. USING THE IBC TABLE 1004.1.2, USE 30 SF PER OCCUPANT, AND REVISE THE OCCUPANCY LOAD ON THE DRAWINGS.
3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
08/04/2016 ROBERT SHERRY WATER REVIEW Reqs Change Provide the water meter size and serial number. Show the location of the water meter and the backflow preventer
08/04/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/05/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
08/17/2016 ARUIZ1 FIRE REVIEW Needs Review Occupant load appears to be calculated incorrectly. Please review numbers. If occupant load has been calculated incorrectly, an additional exit will be required. Exiting through storage area is generally not allowed, unless specific guidelines are followed.