| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/11/2017 | LBOJORQ1 | FIRE | REVIEW | Needs Review | |
| 10/31/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 10/31/2016 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 10/31/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Provide a complete electrical plan. Indicate assigned branch circuit numbers and load center, panel schedule, load calc's and location. Include all conduit, conductor sizes and types. #2. Show the locations of the emergency power off buttons. Ref: 2012 IBC 107.2.1, 2011 NEC |
| 10/31/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/31/2016 | ANDREW CONNOR | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/11/2017 | LBOJORQ1 | OUT TO CUSTOMER | Completed |