Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T16CM06071
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/17/2016 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 08/30/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEETS L-2 AND L-3: THE EXPIRATION DATE FOR THE PROFESSIONAL ENGINEER'S SEAL IS INDICATED AS 3/31/2016, AND THE SEAL WAS SIGNED ON 7/29/2016. PLEASE VERIFY. 2. GENERAL: SECTION R4-30-304 OF THE RULES OF THE ARIZONA STATE BOARD OF TECHNICAL RESISTRATION STATES THAT THE OUTER CIRCLE OF THE REGISTRANT'S SEAL SHALL BE 1-1/2" DIAMETER +/- 1/16". PLEASE REVISE THE SEALS ON ALL DRAWING SHEETS. 3. GENERAL: PLEASE PROVIDE TWO COMPLETE SETS OF THE STRUCTURAL CALCULATIONS WITH THIS SUBMITTAL. 4. GENERAL: PLEASE DARKEN THE INFORMATION ON ALL DRAWING SHEETS AS REQUIRED. MANY SHEETS WILL NOT BE LEGIBLE ONCE ARCHIVED. 5. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 09/08/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/16/2016 | ARUIZ1 | OUT TO CUSTOMER | Completed |