Permit Number: T16CM06062
Parcel: 126210450

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T16CM06062
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/09/2016 MARTIN BROWN FIRE REVIEW Approved
08/29/2016 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T16CM06062
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL COMMENTS:

1. Show compliance with the Pool Barrier requirement by including a pool alarm system for doors and windows open to the pool, or show a continuous barrier around the pool, 2012 IRC Appendix G.

PLUMBING PLANS:

1. Show gas pipe sizes in compliance with connected demand, G2413.3 & Table G2413.4(1). The 3/4" firepit branch and 1" supply gas line between the meter and the firepit branch are undersized.

MECHANICAL PLANS:

1. Provide demand calculations in accordance with Manual J/S/D standards, M1401.3, M1601.1. Systems shall be sized in accordance with Manual S based on building loads calculated in accordance with Manual J and duct systems sized in accordance with Manual D. Notate if the mechanical system calculations may be provided by deferred submittal. The deferred calculations must be approved through revision process prior to mechanical inspections.

ELECTRICAL PLANS:

1. Show Bathroom receptacles on a separate 20 AMP circuit (dedicated) with outlets at no other location (ckt #14), E3703.4. Place the laundry room receptacles on a separate circuit.
2. Show or notate a disconnect means or a locking breaker for the water heater, E4101.5.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/30/2016 FERNE RODRIGUEZ REJECT SHELF Completed