Permit Number - T16CM06019
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/01/2016 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 08/01/2016 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 08/02/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/02/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Revise the ventilation calculations for the Operator/Scheduler room using the occupancy rate shown in Table 403.3, lMC 2012. |
| 08/02/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET TS1; CODE STUDY: A DRINKING FOUNTAIN NOTE INDICATES "N/A EXISTING TO REMAIN". PLEASE LOCATE ON THE BUILDING PLAN (A1). 2. SHEET TS1; CODE STUDY: THE NUMBER OF EXITS NOTE INDICATES "2 EXITS PROVIDED". THE EXIT LOCATED AT OFFICE 108 CAN NOT BE CONSIDERED AN EXIT SINCE THE DOORS 108A AND 108B CAN BE LOCKED (SEE IBC SECTION 1014.2(2)). PLEASE REVISE NOTE. 3. SHEET A1; FLOOR PLAN: PER THE IBC SECTION 1018.4 (EXCEPTION 2), THE ALLOWABLE LENGTH OF A DEAD END CORRIDOR IS 50'. PLEASE INDICATE ON THE PLAN THAT REQUIREMENT IS MET FOR CORRIDOR (PASSAGE) 120. 4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 08/02/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 08/02/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify the size of the fixture drain for the new lavatory; it is 2" on the plumbing plan (1/P1) and 1-1/2" on the riser diagram (1/P2). 2. Clarify the size of the CW branch serving P1 and P2; keynote #5 calls out 1/2" but keynote #6, the note on the plumbing plan (2/P1), and the dimension on the riser diagram show 3/4" for the same pipe. |
| 08/02/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/05/2016 | KROBLES1 | FIRE | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/05/2016 | KROBLES1 | OUT TO CUSTOMER | Completed |