Permit Number: T16CM05964
Parcel: 10713032A

Address:
2700 N STONE AV

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T16CM05964
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/11/2016 ANDREW CONNOR ZONING REVIEW Approved
08/11/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating/cooling load calculations for the new AC units.
2. Show that the owner-provided AC unit meets the requirements of the energy code, IECC 2012.
3. What is being stored in the room served by EF 1A?
08/11/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
08/11/2016 LOREN MAKUS ENGINEERING REVIEW Approved
08/11/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/11/2016 ROBERT SHERRY WATER REVIEW Completed
08/11/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Clarify the reason for AC 2A having two natural gas services.
08/12/2016 MARTIN BROWN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/16/2016 KROBLES1 OUT TO CUSTOMER Completed