Permit Number: T16CM05884
Parcel: 140290280

Address:
3321 E GLOBAL LP

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T16CM05884
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/27/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A1.0; CODE REVIEW: IN THE GENERAL BUILDING SUMMARY, THE OCCUPANCY GROUP FOR BOTH SPACES INDICATES B-2. PLEASE REVISE PER THE IBC SECTION 304.
2. SHEET A1.0; GOVERNING REGULATIONS: PLEASE REVISE THE ACCESSIBILITY CODE THE THE 2012 IBC AND THE 2009 ICC/ANSI A117.1.
3. SHEET A1.0; CODE REVIEW: PLEASE PROVIDE THE SQUARE FOOTAGE AND OCCUPANT LOAD FOR BOTH 3301 AND 3321 SPACES ON THE DRAWINGS.
4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
07/27/2016 ERIC NEWCOMB MECHANICAL-COMMERCIAL REVIEW Passed
07/27/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Passed
07/27/2016 ERIC NEWCOMB PLUMBING-COMMERCIAL REVIEW Passed
07/28/2016 KEN BROUILLETTE FIRE REVIEW Reqs Change FIX BUILDING COMMENTS THEN RESUBMIT