Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T16CM05883
Parcel: 140290290

Address:
3301 E GLOBAL LP

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T16CM05883
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/27/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A1.0; CODE REVIEW: IN THE GENERAL BUILDING SUMMARY, THE OCCUPANCY GROUP FOR BOTH SPACES INDICATES B-2. PLEASE REVISE PER THE IBC SECTION 304.
2. SHEET A1.0; GOVERNING REGULATIONS: PLEASE REVISE THE ACCESSIBILITY CODE THE THE 2012 IBC AND THE 2009 ICC/ANSI A117.1.
3. SHEET A1.0; CODE REVIEW: PLEASE PROVIDE THE SQUARE FOOTAGE AND OCCUPANT LOAD FOR BOTH 3301 AND 3321 SPACES ON THE DRAWINGS.
4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
07/27/2016 ERIC NEWCOMB MECHANICAL-COMMERCIAL REVIEW Passed
07/27/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Passed
07/27/2016 ERIC NEWCOMB PLUMBING-COMMERCIAL REVIEW Passed
07/28/2016 KEN BROUILLETTE FIRE REVIEW Reqs Change FIX BUILDING COMMENTS THEN RESUBMIT