Permit Number: T16CM05759
Parcel: 106070250

Address:
1323 W PRINCE RD

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T16CM05759
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/01/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
09/08/2016 MARTIN BROWN FIRE REVIEW Approved
09/09/2016 PAUL BAUGHMAN ENGINEERING REVIEW Reqs Change DATE: September 9, 2016
DUE DATE: September 27, 2016
SUBJECT: Medical office addition
TO: Gene Goldstein, RA
LOCATION: 1323 W Prince Road
REVIEWERS: Paul Baughman, PE, CFM
ACTIVITY: T16CM05759
SUMMARY: Engineering Division of Planning and Development Services Department has received and reviewed the proposed Development Plan Package. The following items need to be addressed:
1) Please update the Reference Site plan on sheet TS1 and the subsequent 2 DP sheets 1 and 2 to reflect changes requested as part of the DP16-0125 comments.
2) This plan cannot be approved by engineering prior to approval of the DP16-0125 plan.
If you have any comments questions or wish to discuss new information, please call or email me at 520-837-5007 or paul.baughman@tucsonaz.gov.
09/14/2016 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Principle Planner

PROJECT: MHC Healthcare Building Expansion.
T16CM05759
Building Plan (2nd Review)

TRANSMITTAL DATE: September 14, 2016

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. It appears that the proposed building plans matches what is shown on development package DP16-0125 but until the development package is approved the building plans cannot be approve.

3. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
09/22/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
09/22/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
09/30/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. PREVIOUS COMMENT 5; NEW SHEET A1.1; KEYNOTES: NOTE 6 INDICATES A REFERENCE FOR A FIRE EXTINGUISHER. PLEASE CLARIFY THE REFERENCE (2A/10BC).
2. PREVIOUS COMMENT 7; SHEETS A2.0 AND A2.1; ELEVATION KEYNOTES: THE NEW NOTE ADDED ON SHEET A2.1 REFERENCES SHEET A2.1. PLEASE REVISE THIS REFERENCE TO SHEET A2.0.
3. PREVIOUS NOTE 17; SHEET S2.0; BRACING DETAIL 6: PLEASE INDICATE THE MAXIMUM BRACE SPACING ON THE DRAWING (THE DETAIL INDICATES THE MINIMUM NUMBER OF BRACES).
4. PREVIOUS COMMENT 24; STRUCTURAL CALCULATIONS: PLEASE PROVIDE STRUCTURAL CALCULATIONS FOR THE NEW JOIST EXTENSIONS FOR THE CONNECTION DESIGN. THIS WAS NOT FOUND AS REQUESTED.
5. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.