Permit Number: T16CM05704
Parcel: 110163440

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T16CM05704
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/05/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/05/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
10/05/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also include a written response.
#1. The type 'D' luminaires are not included in the revised Comcheck Interior Lighting compliance calc's.
#2. Verify the 75 KVA transformer location and compliance with NEC art. 450.13 B. And power source for the added exhaust fan.
10/05/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
10/12/2016 LBOJORQ1 OUT TO CUSTOMER Completed