Review Date Reviewer's Name Type of Review Description Status Comments
07/28/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Correct the plumbing requirements analysis shown on sheet A0.0. Separate facilities are required for each sex when the occupant load is greater than 15 in a business occupancy. Reference: Section 2902.2, IBC 2012.
2. Show the location of the cups for use with the water dispenser. Reference: Section 107.2.1, IBC 2012.
3. Provide structural calculations for the mounting shelf for the water heater to show that the water heater will be safely supported from the building structure. Finish detailing the construction of the supporting shelf. Reference: Section 301.2, IPC 2012.
4. Verify that the proposed automatic faucet for the lavatories will be set to dispense a maximum of 0.25 gallons per metering cycle and that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-03.
5. Provide tempered water for the restroom lavatories using approved devices conforming to ASSE 1070; the proposed temperature mixing valve is listed to ASSE 1017. Reference: Sections 416.5 and 607.1.2, IPC 2012.
6. Coordinate the waste and vent isometric with the plumbing plan (i.e. there are two P-2 fixtures shown on the plan but only one on the isometric).
07/28/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Demonstrate energy code compliance for the alterations to the building envelope using calculations based on the current code. Reference: Sections C101.4.3, C101.5, C103.2, C303, and C401.2.1, International Energy Conservation Code 2012.
2. Provide the equipment schedules for the rooftop units and show that the rooftop units meet the requirements of Sections C403.2.2, C403.2.3, C403.2, and C403.3 (e.g. provide the mechanical energy code compliance certification from COMcheck). Reference: Section C303.1, International Energy Conservation Code 2012.
07/29/2016 ROBERT SHERRY WATER REVIEW Completed
08/15/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A0.0; BUILDING CODES (CHAPTER 5): IN THE ALLOWABLE AREA CALCULATION, THE AREA MODIFICATION EQUATION INDICATES Aa IS 40,375 SF, WHILE THE NEXT LINE INDICATES ALLOWABLE AREA IS 31,500 SF. PLEASE COORDINATE.
2. SHEET A0.0; BUILDING CODES (CHAPTER 6): THE EXTERIOR BEARING WALLS ARE INDICATED TO HAVE A TWO HOUR FIRE RESISTANCE RATING. THE IBC TABLES 601 AND 602 REQUIRE ONLY A ONE HOUR FIRE RESISTANCE RATING. PLEASE VERIFY. ARE THE EXTERIOR WALLS BEARING?
3. SHEET A0.0; BUILDING CODES (CHAPTER 29): PLEASE INDICATE ON THE DRAWING A HIGH/LOW DRINKING FOUNTAIN OR SINGLE POINT OF USE WATER DISPENSER ARE REQUIRED. PLEASE INDICATE THE LOCATION ON THE PLAN.
4. SHEET A0.0; PROJECT SCOPE OF USE: PLEASE REMOVE THE NOTE "NO CHANGE IN USE", AND SUBSTITUTE THE NOTE 'FIRST TENANT IN'.
5. SHEET A0.0; REFERENCE FLOOR PLAN (SECOND FLOOR): THE DASHED LONGEST EXIT ROUTE SHOULD BE TITLED THE COMMON PATH OF EGRESS TRAVEL, AND SHOULD BE INDICATED FROM THE NORTHWEST CORNER OF THE FILE STORAGE 107 AND STOP AT DOOR 100. AT THIS LOCATION, THE COMMON PATH OF EGRESS TRAVEL ENDS (THERE ARE TWO SEPARATE PATHS TO REACH SEPARATE EXITS). THIS SHOULD BE APPROXIMATELY THE 72'-6" SHOWN ON THE REFERENCE FLOOR PLAN (REQUIRED TO BE LESS THAN 100' PER THE IBC TABLE 1014.3). THE EXIT ACCESS TRAVEL DISTANCE SHOULD ALSO BE INDICATED ON THE DRAWING (AS THE DASHED LINE INDICATES). THIS WILL BE THE COMMON PATH OF EGRESS TRAVEL DISTANCE (PER ABOVE) PLUS THE TRAVEL DISTANCE FROM DOOR 100 TO THE BOTTOM OF THE STAIR (REQUIRED TO BE LESS THAN 300' PER THE IBC TABLE 1016.2). PLEASE REVISE THE PLAN.
6. SHEET A1.0; FLOOR PLAN: THE NORTH AND SOUTH EXTERIOR WALLS ARE INDICATED TO BE TYPE W-4.0 ASSEMBLIES. ARE THESE TWO HOUR FIRE RESISTANCE RATED WALLS PER SHEET A0.0? PLEASE VERIFY.
7. SHEET A1.0; FLOOR PLAN: THE IBC SECTION 1005.7.1 REQUIRES DOORS IN ANY POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE THAN ONE-HALF. THE DOORS 109a AND 110 MIGHT FALL IN THAT CATEGORY. PLEASE INDICATE ON THE DRAWINGS THE REQUIRED MINIMUM CORRIDOR WIDTH (PER THE IBC TABLE 1018.2) AND THE CLEAR CORRIDOR WIDTH REMAINING WHEN THOSE DOORS ARE OPEN MEETS THAT REQUIREMENT.
8. SHEET A1.0; FLOOR PLAN: IN WORK ROOM 101, PLEASE VERIFY THE DETAIL 5/A3.0 IS CORRECT AT THAT LOCATION.
9. SHEET A1.0; FLOOR PLAN: IN WORK ROOM 101, PLEASE VERIFY THE DETAIL 5/A4.2 IS CORRECT AT THAT LOCATION.
10. SHEET A1.0; FLOOR PLAN: IN RECEPTION 100, PLEASE VERIFY THE DETAIL 4/A4.2 IS CORRECT AT THAT LOCATION.
11. SHEET A2.0; REFLECTED CEILING PLAN: IN RECEPTION 100, PLEASE VERIFY THE DETAIL 7/A4.0 IS CORRECT AT THAT LOCATION.
12. SHEET A2.0; REFLECTED CEILING PLAN: IN KITCHEN 108, PLEASE VERIFY THE DETAIL 2/A4.2 IS CORRECT AT THAT LOCATION.
13. SHEET A3.0; PLAN: THIS PLAN TITLE IS CALLED OUT AS THE FLOOR PLAN. PLEASE REVISE.
14. SHEET A4.0 (SECTION 3); SHEET A4.2 (SECTION 7): SECTION 7 IS NOT CLEAR. THE ICC/ANSI SECTION 904 INDICATES A PORTION OF THE SERVICE (RECEPTION) COUNTER MUST BE A MINIMUM OF 36" IN LENGTH AND A MAXIMUM OF 36" ABOVE FINISH FLOOR IN HEIGHT. THE APPROACH TO THIS COUNTER MUST MEET THE CRITERIA OF ICC/ANSI SECTION 403. PLEASE CLARIFY THE DETAIL IS CORRECTLY SHOWN.
15. SHEET A5.0; RESTROOM ELEVATION B: PLEASE INCLUDE AN ELEVATION FOR THE TRANSFER-TYPE SHOWER, INCLUDING GRAB BARS, SHOWER SEAT, CONTROLS, AND HAND SHOWER LOCATIONS PER THE ICC/ANSI SECTION 608.
16. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
08/17/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. IECC data and calc's for the interior lighting (comcheck) is not correct. Verify the square footage and the use is not manufacturing.
#2. Provide overcurrent protection for the 75kva transformer secondary conductors as required per NEC art 240.21C
Ref: 2012 IBC 107.2.1, 2011 NEC