Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T16CM05688
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/12/2016 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 08/19/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET S1; FOUNDATION PLAN: THE MASONRY RETAINING WALLS (179 FEET OF 8" AND 142 FEET OF 12") WERE ADDED TO THE VALUATION OF THIS PROJECT. 2. STRUCTURAL CALCULATIONS (MARTIN, WHITE AND GRIFFIS); DESIGN CRITERIA: PLEASE PROVIDE ONE COPY OF THE SOIL REPORT REFERENCED IN THE DESIGN CRITERIA. 3. GENERAL: ON THIS PROJECT, THE DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE OF THE STRUCTURAL DESIGN (THE WLB GROUP) IS RESPONSIBLE FOR THE REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS PREPARED BY OTHERS (THE CALCULATIONS AND SHOP DRAWINGS OF THE CANOPY STRUCTURE BY MID-WEST STEEL BUILDING COMPANY) PER THE IBC SECTION 107.3.4 AND 107.3.4.1. PLEASE FOLLOW THOSE REQUIREMENTS. 4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/23/2016 | RBENT2 | OUT TO CUSTOMER | Completed |