Permit Number: T16CM05638
Parcel: 128010040

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM05638
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/27/2016 MARTIN BROWN FIRE REVIEW Approved
07/28/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
07/28/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
07/28/2016 ROBERT SHERRY WATER REVIEW Completed
08/10/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
08/12/2016 STEVE SHIELDS ZONING REVIEW Approved
08/18/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A102: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE DESCRIPTION OF WORK TO BE PERFORMED ON PLAN.
2. SHEET A103: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE DESCRIPTION OF WORK TO BE PERFORMED ON PLAN.
3. SHEET A105: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE DESCRIPTION OF WORK TO BE PERFORMED ON PLAN.
4. SHEET A802; REFLECTED CEILING PLAN: PLEASE INDICATE WORK TO BE DONE IN THIS AREA ON THE PLAN.
5. SHEET A803; REFLECTED CEILING PLAN: PLEASE INDICATE WORK TO BE DONE IN THIS AREA ON THE PLAN.
6. SHEET A805; REFLECTED CEILING PLAN: PLEASE INDICATE WORK TO BE DONE IN THIS AREA ON THE PLAN.
7. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/26/2016 BGRANT1 OUT TO CUSTOMER Completed