Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T16CM05592
Parcel: 12101103J

Address:
6268 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM05592
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/19/2016 ANDREW CONNOR ZONING REVIEW Approved
07/19/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
07/19/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
07/19/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
07/19/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
07/19/2016 ROBERT SHERRY WATER REVIEW Reqs Change Verify the existence of a backflow preventer for this meter.
Provide the size of the device and show its location.
07/19/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The water pressure at this location is in excess of 80 PSI. Provide a pressure regulator.
2. Revise the water pressure calculations to include the effects of a backflow preventer and a pressure regulator.
3. The Watts model L111 temperature mixing valve is no longer listed (obsolete product).
4. Provide structural calculations and mounting details for the support of the water heater.
07/19/2016 MARTIN BROWN FIRE REVIEW Approved
07/19/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
07/21/2016 KROBLES1 OUT TO CUSTOMER Completed