Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM05592
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/19/2016 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
07/19/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
07/19/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
07/19/2016 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
07/19/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
07/19/2016 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Verify the existence of a backflow preventer for this meter. Provide the size of the device and show its location. |
07/19/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The water pressure at this location is in excess of 80 PSI. Provide a pressure regulator. 2. Revise the water pressure calculations to include the effects of a backflow preventer and a pressure regulator. 3. The Watts model L111 temperature mixing valve is no longer listed (obsolete product). 4. Provide structural calculations and mounting details for the support of the water heater. |
07/19/2016 | MARTIN BROWN | FIRE | REVIEW | Approved | |
07/19/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/21/2016 | KROBLES1 | OUT TO CUSTOMER | Completed |