Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16CM05476
Parcel: 11004345J

Address:
3305 N SWAN RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM05476
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/14/2016 ANDREW CONNOR ZONING REVIEW Approved
07/14/2016 LOREN MAKUS ENGINEERING REVIEW Approved
07/15/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide complete compliance with the 2012 IECC for interior lighting.
07/15/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Show how the new area will be provided with ventilation since there is no return air for the HVAC system in that room.
07/15/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A1.0: PLEASE PROVIDE A DETAIL ON THIS SHEET INDICATING HOW THE NEW PARTITION WALL IS BRACED AT THE TOP TO RESIST THE LOADS REQUIRED BY THE IBC SECTION 1607.14. INCLUDE BRACING SIZE AND SPACING, CONNECTION TO THE TOP OF THE PARTITION WALL, AND CONNECTION TO THE EXISTING STRUCTURE ABOVE (INCLUDE CONNECTOR SIZE AND QUANTITY).
07/15/2016 ROBERT SHERRY WATER REVIEW Completed
07/15/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
07/15/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/18/2016 KEN BROUILLETTE FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/20/2016 ARUIZ1 OUT TO CUSTOMER Completed