Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16CM05408
Parcel: 11708164B

Address:
501 W 18TH ST 04

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM05408
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/13/2016 ANDREW CONNOR ZONING REVIEW Approved
07/13/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
07/13/2016 MARTIN BROWN FIRE REVIEW Approved
09/09/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
09/09/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
09/09/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/09/2016 ROBERT SHERRY WATER REVIEW Completed
09/09/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
09/09/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
03/16/2017 MMENDIB1 APPROVAL SHELF Completed