Permit Number: T16CM05403
Parcel: 122124080

Address:
1635 N SWAN RD

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T16CM05403
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/16/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/26/2016 ROBERT SHERRY WATER REVIEW Completed
09/26/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The five rooftop AC units installed as part of the building shell are heat pumps; if these units are not to be replaced with AC units with gas heat, revise the gas piping design accordingly. Reference: Section 107.2.1, IBC 2012.
2. Revise the configuration of the natural gas sediment trap, as shown in detail 5/P0.2, to comply with the requirements of Section 408.4, IFGC 2012.
3. The private sewer collection system drawings included with this submittal indicate that a backwater valve is required. Reference: Section 715.1, IPC 2012.
4. Indirect waste receptors shall not be installed in inaccessible or unventilated spaces (e.g. cupboards, storerooms, or closets). Indirect waste receptors shall have ready access. Reference: Sections 202 and 802.3, IPC 2012.
09/26/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. The five rooftop AC units installed as part of the building shell are heat pumps; if these units are to be replaced with AC units with gas heat, provide new specifications. Reference: Section 107.2.1, IBC 2012.
2. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment installed as part of the building shell and AC-2. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012.
3. Revise the sequence of operation for the restroom exhaust fans EF-4 and EF-5 so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). Reference: Section 403.2.1 (4), IMC 2012.
4. Provide a smoke detector in the return air duct, upstream of any outside air connections, for all air distribution systems with a design return air capacity greater than 2,000 CFM. Reference: Section 606.2.1, IMC 2012.
5. Clarify the reason for installing a fire damper in a duct penetrating a non-fire-rated partition at room 103 and not installing a fire damper at the duct penetrations of the 1-hour rated fire partition surrounding room 128. Reference: Section 607.5, IMC 2012.
6. Clarify the reason for installing a fire damper in the duct penetrating a non-fire-rated partition on the west side of room 115 and not installing a fire damper at the duct penetrating the 1-hour rated fire partition on the east side of room 115. Reference: Section 607.5, IMC 2012.
09/28/2016 MARTIN BROWN FIRE REVIEW Approved
09/28/2016 STEVE SHIELDS ZONING REVIEW Approved
10/05/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved