Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM05376
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/12/2016 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 07/12/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 07/12/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/12/2016 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 07/12/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET G-101; CODE REVIEW: PLEASE INDICATE ON THE DRAWINGS IF THIS IS A SPRINKLERED BUILDING. 2. SHEET G-101; GENERAL NOTES: PLEASE REMOVE THE 2010 ADA STANDARDS FOR ACCESSIBLE DESIGN AND REPLACE IT WITH THE 2009 ICC/ANSI A117.1. 3. SHEET A-101; FLOOR PLAN: PLEASE INDICATE ON THE DRAWING THE MANEUVERING CLEARANCE AT THE TWO 'D' DOORS MEETS THE REQUIREMENTS OF THE ICC/ANSI FIGURE 404.2.3.5 (PULL SIDE). 4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 07/12/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 07/12/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 07/12/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 07/13/2016 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | Fire sprinklers required. Please review local amendment to section 903.2.3 of the 2012 International Fire Code. |