Permit Number: T16CM05375
Parcel: 117060620

Address:
238 N 4TH AV

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T16CM05375
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/18/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. PREVIOUS COMMENT 2; ONE HOUR RATED CORRIDOR: SINCE A ONE HOUR RATED CORRIDOR IS REQUIRED, IN ADDITION TO KEYNOTE 10, PROVIDE A PLAN DETAIL OF THE RATED WALLS, AND INDICATE A U.L. NUMBER WITH THAT DETAIL.
2. PREVIOUS COMMENT 2; ONE HOUR RATED CORRIDOR: THE REFLECTED CEILING PLAN INDICATES TYPE X GYPSUM BOARD AABOVE THE WOOD SLAT CEILING. PLEASE PROVIDE A DETAIL OF THE RATED CEILING/SLATS AND INDICATE A U.L. NUMBER WITH THAT DETAIL.
3. SHEET TS1; CODE REVIEW: THE DRAWING INDICATES A DRINKING FOUNTAIN (SINGLE POINT OF USE) IS PROVIDED ON SITE. A RESTAURANT THAT CAN SERVE DRINKS TO THE PATRONS DOES NOT REQUIRE THE DRINKING FOUNTAIN.
4. SHEET TS1; CODE REVIEW: THE OCCUPANT LOAD INDICATES ENCLOSED RESTAURANT SPACE AND EXTERIOR SEATING. PLEASE INDICATE THESE AREAS ON THE SITE PLAN.
5. GENERAL: PLEASE PROVIDE A SITE PLAN PER THE IBC SECTION 107.2.
6. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
07/18/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
07/18/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
07/20/2016 ARUIZ1 ZONING REVIEW Needs Review