Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/18/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. PREVIOUS COMMENT 2; ONE HOUR RATED CORRIDOR: SINCE A ONE HOUR RATED CORRIDOR IS REQUIRED, IN ADDITION TO KEYNOTE 10, PROVIDE A PLAN DETAIL OF THE RATED WALLS, AND INDICATE A U.L. NUMBER WITH THAT DETAIL. 2. PREVIOUS COMMENT 2; ONE HOUR RATED CORRIDOR: THE REFLECTED CEILING PLAN INDICATES TYPE X GYPSUM BOARD AABOVE THE WOOD SLAT CEILING. PLEASE PROVIDE A DETAIL OF THE RATED CEILING/SLATS AND INDICATE A U.L. NUMBER WITH THAT DETAIL. 3. SHEET TS1; CODE REVIEW: THE DRAWING INDICATES A DRINKING FOUNTAIN (SINGLE POINT OF USE) IS PROVIDED ON SITE. A RESTAURANT THAT CAN SERVE DRINKS TO THE PATRONS DOES NOT REQUIRE THE DRINKING FOUNTAIN. 4. SHEET TS1; CODE REVIEW: THE OCCUPANT LOAD INDICATES ENCLOSED RESTAURANT SPACE AND EXTERIOR SEATING. PLEASE INDICATE THESE AREAS ON THE SITE PLAN. 5. GENERAL: PLEASE PROVIDE A SITE PLAN PER THE IBC SECTION 107.2. 6. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
07/18/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
07/18/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
07/20/2016 | ARUIZ1 | ZONING | REVIEW | Needs Review |