Review Date Reviewer's Name Type of Review Description Status Comments
07/12/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/12/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Coordinate the fan coil unit schedule with the COMcheck Mechanical compliance certificate; they appear to be for two different activities.
2. Provide cooling/heating load calculations.
3. Where is EF-2 located?
07/12/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
07/12/2016 LOREN MAKUS ENGINEERING REVIEW Approved
07/12/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A1.0; FLOOR PLAN KEYNOTES: NOTE 13 INDICATES A 'NEW ADA ACCESSIBLE TOILET'. IT IS CALLED OUT ON THE FLOOR PLAN FOR EVERY TOILET. ARE ALL NEW TOILETS ACCESSIBLE? PLEASE VERIFY AND REVISE AS REQUIRED.
2. SHEET A1.0; FLOOR PLAN: PER THE IBC TABLE 1018.1, IF THE NEW CORRIDOR TO THE RESTROOMS SERVES MORE THAN 30 PEOPLE AND IS NON-SPRINKLERED, A ONE HOUR RATING IS REQUIRED. PLEASE INDICATE THE NUMBER OF OCCUPANTS SERVED BY THIS CORRIDOR.
3. SHEET TS1; CODE REVIEW: PLEASE INDICATE THE OCCUPANT LOAD THIS RESTAURANT WILL SERVE, AND PROVIDE A PLUMBING FIXTURE ON THE DRAWINGS.
4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
07/12/2016 ROBERT SHERRY WATER REVIEW Completed
07/12/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide the rim elevation of the next upstream sanitary manhole and the first floor elevation. Determine the need for a backwater valve per Section 715.1, IPC 2012, as amended by the City of Tucson.
07/13/2016 MARTIN BROWN FIRE REVIEW Approved
07/18/2016 RBENT1 ZONING REVIEW Needs Review