Permit Number: T16CM05314
Parcel: 12418162F

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T16CM05314
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/12/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating/cooling load calculations to justify the capacity of the A/C units conditioning the area.
2. Provide COMcheck Mechanical Compliance Certificate to show that the new unit complies with the requirements of the 2012 International Energy Compliance Code.
3. Provide calculations to show that the area has adequate ventilation based on the requirements of Section 403.3, IMC 2012.
07/12/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved