Review Date Reviewer's Name Type of Review Description Status Comments
07/22/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. As per the last review comment #2, circuiting not complete or accurate for the lighting.
#2. As per the last plan review comment #4 Load calc's for the new panel 'LP11' not included in the landlord panel calc's.
Ref: 2012 IBC 107.2.1, 2011 NEC.
07/22/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
08/04/2016 KROBLES1 OUT TO CUSTOMER Completed