Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM05204
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/08/2016 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
07/08/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide calculations demonstrating adequate ventilation using the current code. Reference: Section 403.2, IMC 2012. 2. The occupant load used to calculate the required ventilation is not necessarily the same as the occupant load used for calculating exiting requirements. The occupant load used for calculating the minimum required ventilation is to be based on Table 403.3, IMC 2012 or an approved engineering analysis of the specific occupancy type. Reference: Section 403.3, IMC 2012. |
07/08/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Minimum font lettering size is 3/32" for plan documents.Per City of Tucson Commercial plan Submittal Requirements. #2. Designate branch circuits and panels for all devices, lighting, and equipment. Also indicate if equipment is new or existing. #3. Provide complete compliance with the 2012 IECC for lighting. #4. Provide a complete panel scedule and load calc for the landlord panel to verify capacity for added new panel. Incomplete electrical plan review at this time. Ref: 2012 IBC 107.2.1, 2011 NEC |
07/08/2016 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
07/08/2016 | STANTEC | BUILDING-COMMERCIAL | REVIEW | Completed | |
07/08/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
07/08/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
07/11/2016 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
07/22/2016 | RBENT2 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed |