Review Details: COMMERCIAL - TI

Permit Number - T16CM05124
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/14/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
07/14/2016 ROBERT SHERRY WATER REVIEW Completed
07/15/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide structural calculations and details to show how the three new fan coil units are to be connected to the building structure. Reference: Section 302.1, IMC 2012.
2. Provide the balancing data for the two existing restroom exhaust fans to verify that the fans will be exhausting all of the air being supplied to each restroom. Verify that the fans will be operating whenever HVAC air is being supplied to each restroom during the hours of occupancy. Reference: Section 403.2.1 (4), IMC 2012.
3. Revise the air distribution for the existing 6-ton rooftop unit so that the egress corridor is not used as a duct. Reference: Section 601.2, IMC 2012.
07/22/2016 STEVE SHIELDS ZONING REVIEW Approved
08/03/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved