Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM05124
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/14/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
07/14/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
07/15/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide structural calculations and details to show how the three new fan coil units are to be connected to the building structure. Reference: Section 302.1, IMC 2012. 2. Provide the balancing data for the two existing restroom exhaust fans to verify that the fans will be exhausting all of the air being supplied to each restroom. Verify that the fans will be operating whenever HVAC air is being supplied to each restroom during the hours of occupancy. Reference: Section 403.2.1 (4), IMC 2012. 3. Revise the air distribution for the existing 6-ton rooftop unit so that the egress corridor is not used as a duct. Reference: Section 601.2, IMC 2012. |
07/22/2016 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
08/03/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |