Permit Number: T16CM05052
Parcel: 116211390

Address:
156 S CUESTA AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T16CM05052
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2016 STEVE SHIELDS ZONING REVIEW Reqs Change FROM: Steve Shields, Principal Planner - Zoning Review Section

PROJECT: T16CM05052
156 S. Cuesta Avenue
New Dwelling on an R-2 Parcel

TRANSMITTAL: September 14, 2016

COMMENTS:

This site is located in the R-2 zone (UDC 4.7.9). Multi-family residential is a permitted use in this zone (Table 4.8-2). See Use Specific Standards 4.9.7.B.6, .9 & .10.

1. Addressed. Comment: All references to the second unit should be removed from the plan.

2. This comment was not addressed. Per UDC Article 6.4.3.B.3.b Vehicular use areas, measured within the outside edges of any area allocated to vehicle use, whether improved or unimproved. The provided lot coverage calculation does not include the vehicle use area. Comment: Lot coverage calculations shall include the square footage area of the driveway.
09/19/2016 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T16CM05052 R1
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

PLUMBING PLANS:

1. Remove the outdated code reference at the first note on sheet A.6.

MECHANICAL PLANS:

1. Provide demand calculations in accordance with Manual J/S/D standards, M1401.3, M1601.1. Systems shall be sized in accordance with Manual S based on building loads calculated in accordance with Manual J and duct systems sized in accordance with Manual D. Notate if the mechanical system calculations will be provided by deferred submittal. This document shows cooling demand for sizing the AC system.

ELECTRICAL PLANS:

1. Designate the circuit number at the location of each light fixture, receptacle, appliance and equipment disconnect switch, E3404.12. Add the HVAC circuit to the plan.
2. Provide a panel schedule showing wire size of each circuit or notate the wire size for each protection rating, E3702.2. Add the HVAC circuit to the schedule.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/14/2016 BGRANT1 OUT TO CUSTOMER Completed