Permit Number: T16CM05047
Parcel: 14118620A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM05047
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/10/2016 ANDREW CONNOR ZONING REVIEW Approved
08/10/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. If nail polish is to be applied at the location of the pedicure chairs, provide localxhaust at each station.
2. Revise the ventilation calculations to include the entire suite.
3. Provide the minimum required exhaust for the nail salon - the exhaust for the restroom and the utility room cannot be counted for the nail salon exhaust.
08/10/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
08/10/2016 LOREN MAKUS ENGINEERING REVIEW Approved
08/10/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Show that the installation of the backflow preventors will comply with the manufacturer's requirements for clearances.
08/10/2016 ROBERT SHERRY WATER REVIEW Reqs Change Provide the total demand served by the existing 1-1/2" water meter.
08/11/2016 MARTIN BROWN FIRE REVIEW Approved
08/16/2016 ARUIZ1 BUILDING-COMMERCIAL REVIEW Needs Review
08/16/2016 ARUIZ1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review