Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM05047
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/10/2016 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 08/10/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. If nail polish is to be applied at the location of the pedicure chairs, provide localxhaust at each station. 2. Revise the ventilation calculations to include the entire suite. 3. Provide the minimum required exhaust for the nail salon - the exhaust for the restroom and the utility room cannot be counted for the nail salon exhaust. |
| 08/10/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/10/2016 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 08/10/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Show that the installation of the backflow preventors will comply with the manufacturer's requirements for clearances. |
| 08/10/2016 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Provide the total demand served by the existing 1-1/2" water meter. |
| 08/11/2016 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 08/16/2016 | ARUIZ1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 08/16/2016 | ARUIZ1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |