| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/29/2016 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 06/29/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 06/29/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please designate the correct space number on the electrical plans and panels.Also IECC calc's. Provide for a w/p GFI protected receptacle on the roof for mech equipment servicing. REF: 2012 IBC 107.2.1, 2011 NEC art. 210.63 |
| 06/29/2016 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 06/29/2016 | CLAYTON TREVILLYAN | BUILDING-COMMERCIAL | REVIEW | Completed | PENDING SUITE 160 PART OF SAME PLAN SET |
| 06/29/2016 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | 1. Verify the available water range with Tucson Water. The utility data shows arrange of 30.66 to 37.66 PSI. 2. Provide the manufacturer and model of the reduced pressure backflow prevention device that provides an 8 PSI pressure drop. |
| 06/29/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 06/29/2016 | CTREVIL1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
| 06/30/2016 | MARTIN BROWN | FIRE | REVIEW | Approved |