Permit Number: T16CM05046
Parcel: 14118620A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM05046
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/29/2016 ANDREW CONNOR ZONING REVIEW Approved
06/29/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide a COMcheck Envelope Compliance Certificate for Suite 160, new construction.
06/29/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please designate space numbers correctly on the electrical plans.
Provide a w/p receptacle on the roof for mech equipment servicing.
REF: 2012 IBC 107.2.1, 2011 NEC art. 210.63
06/29/2016 LOREN MAKUS ENGINEERING REVIEW Approved
06/29/2016 CLAYTON TREVILLYAN BUILDING-COMMERCIAL REVIEW Completed
06/29/2016 ROBERT SHERRY WATER REVIEW Reqs Change 1. Verify the available water range with Tucson Water. The utility data shows arrange of 30.66 to 37.66 PSI.
2. Provide the manufacturer and model of the reduced pressure backflow prevention device that provides an 8 PSI pressure drop.
06/29/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
06/29/2016 CTREVIL1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/30/2016 MARTIN BROWN FIRE REVIEW Approved