Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM05046
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/29/2016 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 06/29/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide a COMcheck Envelope Compliance Certificate for Suite 160, new construction. |
| 06/29/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please designate space numbers correctly on the electrical plans. Provide a w/p receptacle on the roof for mech equipment servicing. REF: 2012 IBC 107.2.1, 2011 NEC art. 210.63 |
| 06/29/2016 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 06/29/2016 | CLAYTON TREVILLYAN | BUILDING-COMMERCIAL | REVIEW | Completed | |
| 06/29/2016 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | 1. Verify the available water range with Tucson Water. The utility data shows arrange of 30.66 to 37.66 PSI. 2. Provide the manufacturer and model of the reduced pressure backflow prevention device that provides an 8 PSI pressure drop. |
| 06/29/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 06/29/2016 | CTREVIL1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/30/2016 | MARTIN BROWN | FIRE | REVIEW | Approved |