Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T16CM05043
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/19/2016 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Completed | |
| 09/19/2016 | KEN BROUILLETTE | FIRE | REVIEW | Reqs Change | PLEASE INDICATE ON SITE PLAN THE LOCATION OF THE NEAREST FIRE HYDRANT. IT SHALL BE WITHIN 600 FEET OF ALL PORTIONS OF THE EXTERIOR WALLS AND THIS IS MEASURED AS THE FIRE TRUCK DRIVES. THE TUCSON FIRE HYDRANT MAP DOES NOT INDICATE A FIRE HYDRANT CLOSE ENOUGH. I AM NOT SURE IF YOU ARE SERVED BY ANOTHER WATER DISTRICT.-KEN B. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/05/2016 | BGRANT1 | OUT TO CUSTOMER | Completed |