Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 3RD
Permit Number - T16CM04943
Review Name: REVISION - - 3RD
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/21/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet P1.1: Indirect waste receptors (e.g. P-12) shall be installed in ventilated locations with ready access. Reference: Sections 202 and 802.3, IPC 2012. . 2. Sheet P1.3: Clarify which water heater is located in room 108A - WH-1 or WH-2. Why isn't the water heater shown in water isometric C/P2.0? Reference: section 107.2.1, IBC 2012. 3. Provide a water supply to P-3 in room 246 (not shown on detail 2/P1.4 or in water isometric D/P2.0). Reference: Section 303.2, IPC 2012. 4. Sheet P3.0: revise the tag for the urinal from P-4 to P-3 to agree with the plumbing schedule on P2.0. Reference: section 107.2.1, IBC 2012. |
| 11/27/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Provide evidence that the added 'K7' exterior luminaires are in compliance with the Tucson/Pima County Outdoor Lighting Code. The exterior lighting calcs and luminaire schedule did not provide the necessary information to determine compliance. #2. Show the locations of transformers '1T3', 1T4, and panels 'R307, R308, on the electrical power or site plans. #3. Indicate feeder conduit, conductor sizes and types for transformers '1T2', '1T3', '1T4', on the one line diagram. #4. Provide complete panel schedules for 'R307, 'R308'. Ref; 2012 IBC 107.2.1, 2011 NEC. |
| 11/29/2017 | DAVID RIVERA | ZONING | REVIEW | Reqs Change | FROM: David Rivera PDSD Zoning Review Section PROJECT: T16CM04943 - Casa De los NiƱos Building Plans (Revision) 1120 N 5th Avenue TRANSMITTAL DATE: November 29, 2017 DUE DATE: December 5, 2017 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. COMMENT: Zoning has reviewed the revisions and while the changes made do not affect zoning requirements the revision plan set cannot be approved until all the Commercial Plans Reviewers have reviewed and approved the revised plan set. 2. COMMENT: Zoning will review the plan set on the next submittal and approve the plans if all Commercial Plans Reviewers have approved the plans. 3. COMMENT: Sheet A1.3 is listed as one of the sheets with revisions but was not included in the revised set. If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans |
| 11/29/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify how flexible ducts are able to penetrate fire-rated partitions. Reference: Section 607.1.1, IMC 2012 and Sections 714 and 717, IBC 2012. 2. Show how the duct penetrations of the fire-rated partitions comply with Section 717.5.4, IBC 2012. |
| 11/29/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 12/01/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | T16CM04943 (3rd Revision) 1. All Sheets; Revisions: The architectural title blocks indicate Revisions Delta 1 through Delta 7. Please indicate on the drawings the date these revisions were submitted to the City of Tucson for approval. 2. Sheet A1.3: This sheet is indicated in the Revision List, but the drawing is not included in this submittal. Please provide. 3. Sheet A2.1; Floor Boxes: The Revision List indicates 'added floor boxes. One was found in Conference Room 119. Are there others indicated on this plan? Please verify. 4. Sheet A2.3; Play Structure Millwork: The Revision List indicates the children's play structure millwork was moved to Sheet A5.4. Please verify that is the correct sheet reference. 5. Sheet A3.0; South Elevation #3: The Revision List does not indicate windows updated on the South Elevation, but it appears there are some that have been updated. Please verify. 6. Sheet A3.1: The elevation description in the Revision List of updated windows does not match the Wall Elevation Titles on Sheet A3.1. Please verify. 7. Sheet A5.4; Play Structure Millwork: The Revision List indicates the children's play structure millwork was moved to Sheet A5.4. Please verify that is the correct sheet reference. 8. Sheet S1.4: It appears Revision 6 (Detail 42) was created in May of 2017. Was this revision submitted to the City of Tucson for review? Please verify. 9. Sheets S2.0 and S2.1: It appears Revision2 was created in September of 2016 and Revision 6 was created in May of 2017. Were these revisions submitted to the City of Tucson for review? Please verify. 10. Sheet S2.2; Framing Plan: The Revision List indicates Foundation Plan updates. This is the Second Floor Framing Plan. In addition, the floor construction indicated on the plan was revised near Grid 4 between Grids B and C. These revisions were not submitted to the City of Tucson for review. Please verify. 11. Sheet S2.3: Revision 6 was created in May of 2017. Was this revision submitted to the City of Tucson for review? Please verify. 12. Sheet S2.4: This sheet is indicated in the Revision List, but the drawing is not included in this submittal. Please provide. 13. Sheet S4.0: This sheet is not indicated in the Revision List, but the drawing is included in this submittal. Please clarify. 14. Sheet S4.2: Revision 6 was created in May of 2017. Was this revision submitted to the City of Tucson for review? Please verify. 15. General: Please provide written responses to all review comments. |
| 12/04/2017 | LOREN MAKUS | ENGINEERING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/10/2018 | QJONES1 | APPROVAL SHELF | Completed |
| 01/10/2018 | QJONES1 | OUT TO CUSTOMER | Completed |
| 01/10/2018 | QJONES1 | REJECT SHELF | Completed |