Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T16CM04862
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/27/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEETS PV1.2, PV1.3, AND PV1.4: THESE SHEETS ALL HAVE A NOTE INDICATING 'SEE SCHLETTER STRUCTURAL SHEETS FOR DETAILS'. THERE ARE NO SCHLETTER DETAIL SHEETS INCLUDED IN THIS SUBMITTAL. PLEASE VERIFY AND PROVIDE AS REQUIRED. 2. SHEET PV1.2; EXISTING ROOF FRAMING PLAN: A BUILDING SECTION INDICATED ON THE PLAN IS NOT COMPLETE. PLEASE REVISE. 3. GENERAL: A LETTER FROM SCHNEIDER STRUCTURAL ENGINEERS (DATED AUGUST 30, 2016) INDICATES THREE RESTRICTIONS FOR THE INSTALLATION AND LOCATION OF THE NEW SOLAR MODULES. PLEASE INCLUDE THOSE RESTRICTIONS ON SHEETS PV1.2, PV1.3, AND PV1.4. 4. GENERAL: EXCEPT FOR THE ELECTRICAL SHEETS, THERE IS NO LICENSED PROFESSIONAL'S SEAL ON THE SHEETS. PLEASE PROVIDE. 5. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/30/2016 | RBENT2 | OUT TO CUSTOMER | Completed |