Permit Number: T16CM04740
Parcel: 105102680

Address:
4240 N 1ST AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T16CM04740
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/13/2016 ROBERT SHERRY BUILDING-COMMERCIAL REVIEW Reqs Change 1. Revise the concrete specifications shown on sheet A-13 to correspond to the requirements noted in the geotechnical report (e.g. the report calls for concrete with a minimum 28-day compressive strength of 4,000 PSI, not 3,000 PSI; "??" is not an appropriate specification, etc.). [Initial comment: General: the structural material strengths must be indicated on a full size drawing, including concrete, concrete reinforcing, anchor bolts, etc. Add the geotechnical report reference on the drawings, and any additional information required by the IBC section 107.]
2. All construction documents submitted to the City of Tucson become part of the public record when the permit is issued. The Sabre Industries plans are noted as containing confidential and proprietary information. Remove the proprietary plans from the drawing set; provide non-proprietary drawings to show how the tie-down connections are to be installed. Do not include installation instructions for types of tie-downs that are not applicable to this activity. Reference: Section 107.2.1, IBC 2012. [Initial comment: General: provide sections and details on full size drawings for the required connection plates, connection plate locations, and all anchors for the equipment shelter to the foundation.]
09/22/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/27/2016 BGRANT1 OUT TO CUSTOMER Completed