Permit Number: T16CM04740
Parcel: 105102680

Address:
4240 N 1ST AV

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T16CM04740
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/22/2016 KEN BROUILLETTE FIRE REVIEW Approved
06/30/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also include a written response.
#1. Provide a complete luminaire schedule for the Dusk to Dawn light fixture.
#2. Provide complete compliance with the Tucson/Pima County Outdoor Lighting Code.
#3. Provide complete panel schedules for panels "A" and "POPB".
#4. Provide a complete one-line diagram for the new Electrical Service and associated equipment. Include conduit, conductor sizes and types for all feeders.
#5. Plan sheet A-2 shows a new AT&T Generator and Transfer switch. Why are these not shown on the Electrical plans?
REF: 2012 IBC 107.2.1, 2011 NEC. City of Tucson Commercial Plan Submittal Requirements.
07/08/2016 LOREN MAKUS ENGINEERING REVIEW Approved
07/13/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. GENERAL: THE NEW MONOPOLE FOUNDATION MUST BE SHOWN ON A FULL SIZE DRAWING, INCLUDING ANCHORAGE OF THE MONOPOLE TO THE FOUNDATION.
2. GENERAL: THE STRUCTURAL MATERIAL STRENGTHS MUST BE INDICATED ON A FULL SIZE DRAWING, INCLUDING CONCRETE, CONCRETE REINFORCING, ANCHOR BOLTS, ETC. ADD THE GEOTECHNICAL REPORT REFERENCE ON THE DRAWINGS, AND ANY ADDITIONAL INFORMATION REQUIRED BY THE IBC SECTION 107.
3. GENERAL: PROVIDE SECTIONS AND DETAILS ON FULL SIZE DRAWINGS FOR THE REQUIRED CONNECTION PLATES, CONNECTION PLATE LOCATIONS, AND ALL ANCHORS FOR THE EQUIPMENT SHELTER TO THE FOUNDATION.
4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
07/18/2016 FRODRIG2 COMMUNICATIONS REVIEW Approved LETTER SENT TO RECORDS

Final Status

Task End Date Reviewer's Name Type of Review Description
07/21/2016 RBENT2 OUT TO CUSTOMER Completed