Permit Number: T16CM04701
Parcel: 11303077A

Address:
3700 N 1ST AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM04701
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/17/2016 ANDREW CONNOR ZONING REVIEW Approved
06/17/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Show that the ventilation in the new restroom complies with Section 403, IMC 2012.
06/17/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
06/17/2016 LOREN MAKUS ENGINEERING REVIEW Approved
06/17/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET TS1; PROJECT CODE REVIEW (OCCUPANT LOADS): PER THE IBC TABLE 1004.1.2, THE EXERCISE ROOM OCCUPANT LOAD MUST BE CALCULATED AT 50 SF/PERSON. PLEASE REVISE ON THE DRAWINGS.
2. SHEET A1.0; FLOOR PLAN: KEYNOTE 23 (LOCATED AT THE SIDEWALK) IS NOT INDICATED IN THE CORRECT LOCATION. PLEASE REVISE.
3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
06/17/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/20/2016 KEN BROUILLETTE FIRE REVIEW Approv-Cond OCCUPANT LOAD WILL BE FIXED PER BUILDING REVIEW
06/21/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/22/2016 KROBLES1 WATER REVIEW Needs Review