Permit Number: T16CM04683
Parcel: 11620636B

Review Status: Completed

Review Details: REVISION - - 4TH

Permit Number - T16CM04683
Review Name: REVISION - - 4TH
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/15/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The location of the building sewer from building G6.1 has changed on sheet P1.3 but sheet P1.0 and the civil plan have not been revised to show the new location. Coordinate the drawings.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/22/2017 KROBLES1 OUT TO CUSTOMER Completed