Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T16CM04640
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/27/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 07/27/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Verify where the temperature and pressure relief of the existing water heater located in the utility closet terminates. Termination of the excess pressure relief from the water heater over an elevated service sink (such as the one you are proposing) is not approved location. Reference: Section 504.6 (6), IPC 2012. [Initial comment: Provide the minimum plumbing fixtures (e.g. drinking fountains and service sink) required by Table 2902.1 and Section 2902.2, IBC 2012, for business occupancy.] 2. Add a note to the drawing to require that, "All plumbing fixtures shall be listed by a third-party certification agency as complying with the referenced standards." Reference: Section 303.4, IPC 2012. [Initial comment: Provide fixture descriptions for all plumbing fixtures. Reference: Section 402, IPC 2012 and Section 107.2.1, IBC 2012.] 3. With respect to the proposed water mister system for the south ramada, the water supply to the system shall be protected by the installation of a reduced pressure principle backflow prevention assembly (ASSE 1013). Reference: Section 608.16.6, IPC 2012. |
| 08/01/2016 | ARUIZ1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |