Permit Number: T16CM04640
Parcel: 121136370

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM04640
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/12/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET TL-1; PROJECT KEYNOTES: IN NOTE 2, PLEASE INDICATE THE STUD MATERIAL, SIZE, AND SPACING, OR PROVIDE A REFERENCE TO A DETAIL, PLAN, OR NOTE INDICATING THE WALL CONSTRUCTION.
2. SHEETS TL-1, EX-1, A-0, AND A-1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THESE SHEETS.
3. SHEET A-1; PROJECT KEYNOTES: IN NOTES REQUIRING NEW STUD WALLS, PLEASE INDICATE THE STUD MATERIAL, SIZE, AND SPACING, OR PROVIDE A REFERENCE TO A DETAIL, PLAN, OR NOTE INDICATING THE WALL CONSTRUCTION.
4. SHEET A-5; NOTE AT NEW SOUTH RAMADA: IN THIS NOTE, REFERENCE SHEETS S-1 AND S-2 FOR ADDITIONAL RAMADA INFORMATION.
5. SHEET A-6; NOTE AT NEW NORTH RAMADA: IN THIS NOTE, REFERENCE SHEETS S-1 AND S-2 FOR ADDITIONAL RAMADA INFORMATION.
6. SHEET A-8; SCHEMATIC PLAN A: PLEASE REVISE THE NOTE "4'-8" DEEP X 2'-6" WIDE CLEAR FLOOR AREA AT LAVATORY" TO 4'-0" DEEP X 2'-6" WIDE CLEAR FLOOR AREA AT LAVATORY.
7. SHEET A-9: A NOTE INDICATES "FOR REFERENCE ONLY". PLEASE REVISE.
8. GENERAL: PLEASE DARKEN SOME VERBIAGE, BUILDING LINES, AND DIMENSIONS ON VARIOUS SHEETS AS THEY ARE DIFFICULT TO READ AND MAY NOT SHOW UP WHEN ARCHIVED.
9. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
07/13/2016 ROBERT SHERRY WATER REVIEW Completed
07/14/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The International Plumbing Code, 2012, and the International Mechanical Code, 2012 are the controlling codes for this activity, not the International Residential Code. Revise the plumbing and mechanical notes on sheet MP-1 to reference the correct codes and eliminate any notes that do not apply to this activity. Reference: Section 101.2, IPC 2012.
2. Provide the minimum plumbing fixtures (e.g. drinking fountains and service sink) required by Table 2902.1 and Section 2902.2, IBC 2012, for business occupancy.
3. Provide fixture descriptions for all plumbing fixtures. Reference: Section 402, IPC 2012 and Section 107.2.1, IBC 2012.
4. Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-03.
5. Provide tempered water for the lavatory using an approved device conforming to ASSE 1070. Reference: Sections 303.2 and 416.5, IPC 2012.
07/14/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Revise the sequence of operation for the restroom exhaust fan that is being modified so that all of the air supplied to the restrooms will be exhausted (i.e. the restroom fan shall operate continuously during hours of operation). Reference: Section 403.2.1 (4), IMC 2012.